Appendix D: Legionella Testing Protocols

Document Navigation for "MD 15161 – 2013 Control of Legionella in Mechanical Systems"

Definitions

NLPL:
Non-Legionella Pneumophila Legionella
TBC:
Total bacteria count
CFU:
Colony Forming Units
LPTOT:
Legionella Pneumophila (total all serogroups)
LPSG1:
Legionella Pneumophila Serogroup 1
Culture Test:
Legionella bacterial culture test in accordance with ISO 11731
CFU/ml:
Colony Forming Units per millilitre

Fig 1: Cooling Tower Test Protocol, Normal Mode

Fig 1: Cooling Tower Test Protocol, Normal Mode – Image description below

Image Description

Figure 1 describes the minimum bacterial testing and frequency requirements for cooling towers during normal operation and the required actions based on the testing results. For more information, please consult clauses 3.5.5, 3.5.6 and 3.5.7.

1.4 Acronyms

Fig 2: Open Water System Test Protocol, Normal Mode

Fig 2: Open Water System Test Protocol, Normal Mode – Image description below

Image Description

Figure 2 describes the minimum bacterial testing requirements for open water systems during normal operation and the required actions based on the testing results. For more information, please consult clauses 4.4.5, 4.4.6 and 4.4.

1.4 Acronyms

Fig 3: Humidifier Test Protocol, Normal Mode

Fig 3: Humidifier Test Protocol, Normal Mode – Image description below

Image Description

Figure 3 describes the minimum bacterial testing requirements for humidifiers during normal operation and the required actions based on the testing results. For more information, please consult clauses 5.3.8 and 5.3.9.

1.4 Acronyms

Fig 4: Hot Water Systems Test Protocol, Normal Mode

Fig 4: Hot Water Systems Test Protocol, Normal Mod – Image description below

Image Description

Figure 4 describes the minimum bacterial testing requirements for domestic hot water systems during normal operation and the required actions based on the testing results. For more information, please consult clauses 6.4.19 and 6.4.20.

1.4 Acronyms

Document Navigation for "MD 15161 – 2013 Control of Legionella in Mechanical Systems"