Chapter 4: Open water systems

Document navigation for "Mechanical design 15161—2013 control of Legionella in mechanical systems"

4.1 General

4.2 Design requirements

4.3 Operation and maintenance

4.4 Minimum bacterial testing requirements

Water sampling locations

Bacterial testing results

Minimum bacterial testing requirements and frequency (normal operation)

Minimum bacterial testing requirements (emergency mode)

Dipslide testing limits and actions

Legionella bacteria culture testing limits and actions

Quantitative polymerase chain reaction testing limits and actions

4.5 Operation, maintenance and testing schedule

Table summary

This table indicates a summary of the minimum frequency for operation, maintenance and testing requirements of open water systems.

Table 4.1: Open water systems operation and maintenance and testing summary
Activity Item Frequency
Operation & maintenance Inspection Weekly
Cleaning Weekly
Disinfection When required by bacterial testing results
Testing Dip-slide test Weekly, when system is in operation
Legionella bacteria culture test
  • When dip-slide test results indicate TBC > 100,000 cfu
  • When a qPCR test results indicate Legionella Pneumophila  100 GE/mL
  • Every two months when system is in operation
qPCR test
  • Weekly, when used during emergency mode
  • 24 hours after completion of the system start-up cleaning and disinfection
  • When a Legionella culture test results indicate LPTOT  10 cfu/mL
  • When a qPCR test results indicate Legionella Pneumophila > 100 GE/mL