Chapter 6: Domestic water systems

Document navigation for "Mechanical design 15161—2013 control of Legionella in mechanical systems"

6.1 General

Table summary

This table states how the new hot and cold water systems, piping between the faucet and the circulating mains shall be.

Table 6.1: Maximum pipe system length
Pipe Size Maximum length between faucet and circulating main, metres
Nominal pipe size (NPS) ½ 10
NPS ¾ 5
NPS 1 2

6.2 Cold water systems

Design requirements

Operation & maintenance

Inspection

Disinfection

Minimum bacterial testing requirements

6.3 Operation, maintenance and testing schedule for cold water systems

Table summary

This table indicates a summary of the minimum frequency for operation, maintenance and testing requirements of cold water systems.

Table 6.2: Cold water systems operation and maintenance and testing summary
Activity Item Frequency
Operation & maintenance Inspection
  • Every 5 years: for the presence of pipes serving fixtures that experience periods of prolonged water stagnation at water temperatures between 20 and 50 degrees Celsius
  • Annual: drinking fountains for signs of microbial growth
Disinfection
  • When required by bacterial testing results
  • When potable water systems suspected as Legionella source
Testing Residual oxidant concentration
  • Monthly on the incoming building water supply if the building is not fed by a municipally treated water supply or if concerns have been identified with the municipally treated water supply.

6.4 Hot water systems

Design requirements

Start-up and commissioning

Operation and maintenance

Disinfection

Minimum bacterial testing requirements

Water sampling locations

Bacterial testing results

Minimum bacterial testing requirements and frequency (normal operation)

Minimum bacterial testing requirements (emergency mode)

Dipslide testing limits and actions

Legionella bacteria culture testing limits and actions

Quantitative polymerase chain reaction testing limits and actions

6.5 Operation, maintenance and testing schedule for hot water systems

Table summary

This table indicates a summary of the minimum frequency for operation, maintenance and testing requirements of hot water systems.

Table 6.3: Hot water systems operation and maintenance and testing summary
Activity Item Frequency
Operation & maintenance Inspection
  • During start-up procedure for hot water tanks
  • Verify hot water storage temperature set-point:
  • Monthly, for systems connected to shower facilities (including emergency showers)
  • Annually for systems that serve multiple areas in the building and are not connected to showers
Cleaning
  • Annual
  • When required by bacterial testing results
Disinfection
  • When required by bacterial testing results
  • When potable water systems suspected as Legionella source
Testing Dip-slide test
  • Monthly, if hot water storage temperature is below 50 °C
Legionella bacteria culture test
  • When dip-slide test results indicate TBC > 10,000 cfu
  • When a qPCR test results indicate Legionella Pneumophila  100 GE/mL
  • Every six months for the most remote shower facility
  • Annually, at the most remote fixture, for systems with a storage temperature below 50 °C that serve multiple areas in a building and are not connected to showers
qPCR test
  • Monthly, when used during emergency mode
  • When a Legionella culture test results indicate LPTOT  10 cfu/mL
  • When a qPCR test results indicate Legionella Pneumophila > 100 GE/mL

Document navigation for "Mechanical design 15161—2013 control of Legionella in mechanical systems"